• 24VDC output. • 6.5 amp max total alarm current. • 115VAC 60Hz., 1.45 amp. • Short circuit and thermal overload protection. • Built-in charger for sealed lead acid or gel type battery backup. • Maximum charge current .7 amp. • Zero voltage drop upon transfer to battery backup. • AC input and DC output LED indicators. • AC fail supervision (form "C" contact rated @ 1 amp 28VDC). • Low battery and battery presence supervision (form "C" contact rated @ 1 amp 28VDC).
• Class 2 Rated power limited outputs. • Two (2) Class A or two (2) Class B FACP inputs. • Two (2) Class A or four (4) Class B Indicating Circuits. • Two (2) Class B outputs may be paralleled for more power on an indicating circuit. • One (1) Aux. Power Output @ 1 amp supply current (w/Battery Back Up). • Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and
unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occured on one or more signaling circuit outputs. • 2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. • Horn/Strobe sync protocols include: Wheelock, Gentex, System Sensor, Faraday, Amseco. • Temporal Code 3 Mode. • Steady Mode. • Input to Output Follower Mode (maintains synchronization of notification appliance circuits). • March Time. • Compatible with 24VDC fire panels. • Common Trouble inputs and outputs.
• Accommodates up to two (2) 12VDC/12AH batteries. • Dimensions: 15.5”H x 12”W x 4.5”D. • 1/2" and 3/4" combination knockouts.
Data Sheet
|